Generator Excitation System Faults | Troubleshooting Guide

 

The generator excitation system is essential for regulating voltage and ensuring stable generator operation. Faults in this system can lead to serious operational issues, including voltage instability, over- or under-excitation, and protective relay trips. Understanding generator excitation system faults, their symptoms, root causes, and troubleshooting methods is crucial for engineers and maintenance professionals. This guide provides a comprehensive overview of the most common issues and detailed approaches to resolving them efficiently.

1. What are the common faults in a generator excitation system?

The excitation system is prone to several faults that can affect generator performance:

  • Loss of excitation: complete interruption of field current, resulting in low voltage output.

  • Field current fluctuations: irregular or oscillating field current leading to voltage instability.

  • Over-excitation or under-excitation: triggering alarms or protective relays.

  • Exciter diode or brush failure: preventing proper excitation current flow.

  • AVR malfunction: inability to maintain correct voltage levels.

Detection and prevention: Regular inspection of the AVR, exciter, and field circuits can identify deteriorating components before they cause operational failures. Monitoring field current and voltage trends helps detect abnormalities early.

Read about: Generator Load Sharing Problems | Symptoms, Causes, and Fixes

2. Why does the excitation voltage drop suddenly during operation?

Sudden drops in excitation voltage are commonly observed as an immediate reduction in terminal voltage under load.

Possible causes:

  • Loose or corroded connections in the field circuit or AVR terminals.

  • Worn exciter brushes or contamination on slip rings.

  • Failure of diodes in a brushless exciter.

  • Insufficient or unstable input to the AVR.

Troubleshooting methods:

  1. Measure field voltage and current using appropriate meters.

  2. Inspect all connections for tightness and cleanliness.

  3. Test exciter diodes and AVR output signals.

  4. Check resistance of field windings to ensure continuity.

Preventive practices: Perform regular cleaning of terminals and brushes, monitor field voltage trends, and verify AVR operation periodically to avoid sudden voltage drops.

3. How to diagnose Loss of Excitation in a generator?

Loss of excitation occurs when the field winding receives no current, causing voltage to drop and potentially triggering generator protective relays.

Symptoms:

  • Rapid voltage decline under load.

  • Low reactive power output.

  • Tripping of protection relays due to under-voltage.

Diagnostic approach:

  • Measure AVR output and compare with expected values.

  • Inspect exciter diodes and rectifiers for open or short circuits.

  • Verify continuity and resistance of field windings.

  • Check for open circuits in the excitation field path.

Preventive measures: Ensure proper maintenance of exciter components, verify AVR calibration, and check field circuit continuity periodically.

4. What causes field current imbalance or fluctuation?

Field current imbalance leads to irregular generator voltage and can affect stability.

Causes include:

  • Unequal excitation in multi-phase systems.

  • Loose or corroded connections.

  • Partial failure of exciter components or AVR.

  • Electrical interference or grounding issues.

Testing methods:

  • Measure field current in each phase.

  • Inspect wiring for integrity and secure connections.

  • Verify proper grounding and absence of interference.

Preventive tips: Regularly inspect excitation wiring, maintain clean and tight connections, and use quality insulation to reduce interference.

5. How to identify faulty components in the AVR or exciter circuit?

Symptoms of faulty components:

  • Unstable generator voltage.

  • Over- or under-excitation alarms.

  • Inconsistent field current readings.

Testing methods:

  • Visual inspection of AVR and exciter boards for burned components or corrosion.

  • Measure voltages and resistances in the field and AVR circuits.

  • Use functional testing to simulate excitation input and observe generator response.

Preventive practices: Periodic inspection of AVR and exciter circuits and early replacement of deteriorated components.

6. What are the symptoms of a failed exciter diode or brushless exciter?

Diode failure indicators:

  • No field current generated.

  • Terminal voltage drops even under stable load.

  • Excessive heat in the exciter assembly.

Brushless exciter failure indicators:

  • Irregular voltage fluctuations.

  • Oscillating field current readings.

  • Abnormal electrical signals detected during testing.

Resolution: Test diodes using a multimeter or diode tester, replace faulty components, and verify stable field current after repair.

7. How to test excitation system stability under load?

Testing procedure:

  • Apply varying load conditions and monitor generator voltage and field current.

  • Record voltage and current responses over time.

  • Check for oscillations or delayed response in the excitation system.

Tools required: Multimeter, clamp meter, or digital data logger.

Preventive practice: Regular stability tests ensure the excitation system can respond properly to load changes and maintain voltage regulation.

8. What happens if the excitation system response is too slow?

Slow response can result in voltage drops or instability under dynamic load conditions.

Causes:

  • Low AVR gain or incorrect response settings.

  • Excessive resistance or inductance in the field circuit.

  • Aging exciter components reducing responsiveness.

Testing: Evaluate AVR response time and observe voltage behavior under load changes. Adjust AVR settings and inspect components as needed.

Preventive measures: Periodically review AVR settings and maintain the exciter components to ensure fast response.

9. Why does the generator voltage remain low even after increasing excitation?

Possible causes:

  • Shorted turns in rotor windings.

  • AVR malfunction or improper calibration.

  • Field circuit continuity issues.

  • Excessive load beyond generator rating.

Testing approach: Measure field winding resistance, verify AVR output, and check field circuit integrity.

Preventive practice: Ensure proper calibration of the AVR and regular field circuit inspections.

10. How to troubleshoot over-excitation or under-excitation alarms?

Over-excitation causes:

  • AVR output exceeds set voltage.

  • Faulty sensing or feedback circuit.

Under-excitation causes:

  • Loss of field current.

  • Malfunctioning exciter.

Troubleshooting: Check field current, inspect exciter and AVR, verify voltage feedback, and adjust settings as needed.

Preventive measures: Monitor field current trends and periodically calibrate AVR.

11. What causes hunting (voltage oscillation) in excitation control?

Causes:

  • Incorrect AVR gain or tuning.

  • Electrical noise in field circuits.

  • High system reactance or poor feedback loop stability.

Testing methods: Observe voltage oscillation patterns and check AVR tuning. Use filtering or shielding for electrical noise mitigation.

Preventive measures: Correct AVR tuning and proper electrical design of the field circuit.

12. How to perform insulation resistance and polarity tests on the exciter field?

Insulation resistance testing:

  • Measure resistance between field windings and ground using a megger.

  • Low readings indicate insulation deterioration.

Polarity testing:

  • Ensure correct field connection to the AVR.

  • Wrong polarity may lead to improper excitation and voltage regulation issues.

Preventive practice: Conduct tests regularly to detect insulation failures early.

13. When should you replace exciter brushes or rotating diodes?

Indicators:

  • Brushes below manufacturer wear limits.

  • Diodes showing open or short circuits.

  • Persistent voltage instability.

Preventive measure: Schedule replacement during routine maintenance to avoid sudden failure.

14. Can a weak power supply or AVR input affect excitation voltage?

Yes, weak input can cause:

  • Inadequate excitation current.

  • Voltage instability.

  • AVR malfunction.

Testing: Measure input voltage to AVR and ensure it meets required specifications.

Preventive tips: Maintain a stable DC supply to AVR and check input voltage regularly.

15. How to ensure proper synchronization after excitation fault repair?

Steps:

  • Verify field current and voltage are stable.

  • Ensure AVR operates correctly.

  • Synchronize generator with bus by checking voltage, frequency, and phase alignment.

  • Observe load sharing and voltage regulation performance.

Preventive practice: Post-repair checks are critical to prevent recurrence of excitation faults.

Conclusion

The generator excitation system is vital for reliable and stable generator operation. By understanding the common faults, symptoms, and troubleshooting techniques, engineers can identify and resolve issues effectively. Regular inspection, monitoring, and maintenance of the exciter and AVR prevent unplanned downtime and ensure safe, stable generator performance.


Comments

Popular posts from this blog

VFD Fault Codes: Common Errors and How to Fix Them

Difference Between IE2 and IE3 Motor Efficiency Explained

Variable Frequency Drive Troubleshooting Guide