Generator Synchronization Failures | Root Causes and Prevention



 cement plants, water treatment facilities, hotels, or large manufacturing plants, generators often operate in parallel to meet load demands reliably. Generator synchronization failures can cause serious consequences, including equipment damage, unplanned downtime, unstable parallel operation, and even safety hazards.

Despite the importance, many engineers and technicians encounter recurring problems in the field. This article addresses the 20 most common questions from industrial engineers and provides detailed explanations, practical troubleshooting steps, and preventive measures. By the end of this guide, you will have a comprehensive understanding of generator synchronization and how to prevent failures.

1. What Causes Generator Synchronization Failures?

Synchronization failure occurs when the incoming generator cannot safely connect to the bus or another generator in parallel. Common causes include:

  1. Voltage mismatch: Even small differences in voltage (typically 5–10%) prevent the breaker from closing.

  2. Frequency difference: Generators must match frequency precisely. Deviations as small as ±0.2 Hz can trigger protective devices.

  3. Phase angle error: Phase angle differences greater than 10° produce high circulating currents when the breaker closes.

  4. Incorrect phase sequence: Wrong phase order can instantly damage the generator, breaker, or load equipment.

  5. Equipment or sensor faults: PT/CT inaccuracies or malfunctioning synchronizing relays contribute to failures.

Field Tip: Always measure parameters directly at the synchronization panel before attempting breaker closure. Do not rely solely on display meters.

Read About: Generator Overheating Problems | Causes, Prevention, and Fixes

2. Why Do Synchronizing Relays Reject Closing Even When Readings Seem Correct?

This is a common field problem. Some reasons include:

  • Signal delays from PTs and CTs: Weak signals or loose connections cause relay misinterpretation.

  • Processing delay in PLC-based systems: Minor parameter changes during processing time block the breaker.

  • RPM fluctuations: Slight variations in engine speed can temporarily disrupt voltage or frequency.

  • Environmental conditions: Electrical noise or transient voltage spikes affect relay operation.

Solution: Use data loggers or PLC trend monitoring to capture real-time voltage, frequency, and phase angle readings during synchronization attempts.

3. Standard Limits for Safe Synchronization

  • Voltage difference: ±10%

  • Frequency difference: ±0.2 Hz

  • Phase angle difference: <10°

If these limits are exceeded, the synchronizing relay prevents the breaker from closing to protect equipment.

Practical Example: In a cement plant, even a 1.5% voltage difference on a 6.6 kV generator caused the breaker to block repeatedly until PT calibration was corrected.

4. Detecting Phase Sequence Errors

Phase sequence errors are dangerous and must be verified before synchronization:

  • Use phase rotation meters or digital synchronizers.

  • PLC systems provide alarms for “Reverse Phase Sequence.”

  • Always check both the incoming generator and the bus.

Field Experience: Some technicians overlook phase rotation after maintenance, leading to breaker trips and generator downtime.

5. Can Synchronization Failures Damage Equipment?

Absolutely. Improper synchronization can cause:

  • High circulating currents damaging rotor windings.

  • Torque shocks causing mechanical stress.

  • AVR and governor stress leading to voltage instability.

Case Study: In a hotel generator setup, an incorrect phase angle caused the rotor shaft to experience torsional stress, requiring mechanical inspection and balancing.

6. Manual vs Automatic Synchronization

  • Manual: Operators adjust voltage and speed while observing a synchroscope.

  • Automatic: Synchronizer modules or PLCs automatically align generator voltage, frequency, and phase.

Benefit: Automatic synchronization reduces human error and ensures accurate parallel operation.

7. Why Does Synchronization Work for One Generator but Fail for Another?

Factors causing this include:

  • AVR tuning differences

  • Governor response variation

  • CT/PT calibration discrepancies

  • Mechanical characteristics

Recommendation: Test each generator individually for response speed, AVR voltage response, and governor frequency adjustment.

8. Troubleshooting Intermittent Failures

Common field checks:

  • Tighten all PT/CT connections.

  • Shield control wiring from electromagnetic interference.

  • Monitor engine RPM stability.

  • Use PLC or data logging to capture transient mismatches.

9. How Synchronizing Relays Work

For example, ABB SYNCHROTACT or DEIF AGC series:

  • Continuously measures voltage, frequency, and phase angle.

  • Grants a Close-Permit Signal only if parameters are within set thresholds.

  • Blocks breaker closure otherwise, protecting generators.

Field Tip: Periodically verify relay calibration and settings.

10. Generator Panel Interaction with AVR and Governors

  • Synchronizers send voltage raise/lower commands to the AVR.

  • They send speed/frequency adjustments to governors.

  • Fine-tuning ensures the generator is perfectly aligned with the bus.

Case Example: A cement plant using three 2 MW generators relied on automatic synchronizers to correct a 0.15 Hz frequency difference before closing breakers.

11. Breaker Trips Immediately After Synchronization

Causes:

  • Reverse power flow

  • Reactive power imbalance

  • Improper breaker interlocks

  • CT polarity errors

Field Solution: Verify load distribution, check CT polarities, and adjust AVR/governor settings.

12. Sync-Check Relay (ANSI 25) Role

  • Confirms voltage, frequency, and phase alignment.

  • Prevents premature manual closure.

  • Protects generators from high circulating currents.

Best Practice: Annual functional testing under simulated conditions.

13. PT/CT Wiring Issues

  • Loose or reversed PTs cause incorrect phase comparison.

  • Always verify PT readings at the panel.

Tip: Label all CT/PT wiring during installation to reduce human errors.

14. Preventive Testing

  • CT/PT polarity checks

  • Synchronizer module calibration

  • Breaker close-delay verification

  • Phase rotation checks

  • PLC analog input verification

Field Practice: Conduct these tests before commissioning new generators or after maintenance.

15. Load Sharing Problems After Synchronization

  • Improper AVR/governor settings cause uneven load sharing.

  • Adjust droop and governor tuning for balanced active and reactive loads.

Example: In a multi-generator water plant, adjusting 5% droop on each AVR ensured equal reactive power sharing.

16. Testing Synchronization Protection (ANSI 25F)

  • Inject mismatched voltage/frequency signals.

  • Verify breaker remains blocked.

  • Ensures the system works before live operation.

17. SCADA Monitoring for Synchronization

  • Logs voltage, frequency, and phase angle in real-time.

  • Trend analysis identifies parameter drift.

  • Helps predict potential failures before they occur.

18. Predictive Maintenance Applications

  • Track small deviations in synchronization time or breaker delays.

  • Detect failing sensors, unstable governors, or weak AVRs.

  • Prevents unplanned downtime.

19. Best Practices

  • Use digital automatic synchronizers

  • Tune governors and AVRs properly

  • Shield PT/CT wiring from interference

  • Test under load after control panel updates

20. Recommended Synchronization Systems

  • ABB SYNCHROTACT 5 – High precision

  • DEIF AGC series – PLC-friendly

  • Woodward EasyGen – Multi-generator plants

Field Tip: Using proven systems reduces synchronization failures and extends generator lifespan.

Conclusion

Generator synchronization failures are critical issues in industrial power systems. Causes can be electrical, mechanical, or control-related. Engineers can prevent failures by:

  • Performing proper calibration

  • Conducting preventive maintenance

  • Monitoring parameters in real-time via SCADA

  • Using reliable synchronization systems

Comments

Popular posts from this blog

Synchronous vs Asynchronous Motors: Full Comparison

VFD Fault Codes: Common Errors and How to Fix Them

Difference Between IE2 and IE3 Motor Efficiency Explained